| Voltage measurement | 4.0 ... 600.0 V RMS Value ± 0.5% of the measured value ± 5 digits / 0.1 V |
| PEAK voltage (> 10V) | 50 Hz - 60 Hz / ± 5% ± 50 digits |
| Current measurement | 4.0 ... 1500.0 A true ± 1% V of the measured value ± 5 digits / 0.01 A |
| PEAK current (> 20A) | 50 Hz - 60 Hz / ± 5% ± 50 digits |
| Active power P |
10 W ... 9999 kW in 5 measurement ranges ± 1% of the value + 20 digits (>20 V and >20 A) ± 2% of the value + 40 digits (>20 V and >20 A) 0.1 W ... 1 kW according to the measurement range |
| Apparent power S |
10 VA ... 9999 kVA in 5 measurement ranges ± 1% of the value + 20 digits (>20 V and >20 A) ± 2% of the value + 40 digits (>20 V and >20 A) 0.1 VA ... 1 kVA according to the measurement range |
| Reactive power Q |
10 VAR ... 9999 kVAr in 5 measurement ranges ± 1% of the value + 20 digits (>20 V and >20 A) ± 2% of the value + 40 digits (>20 V and >20 A) 0.1 VAr ... 1 kVAr according to the measurement range |
| Power factor PF |
0.000 ... 1.000 ± 0.04 (>20 V >20 A) / 0.001 ± 0.1 (>20 V >20 A) / 0.001 |
| Phase angle |
-180 ... +180 / ±1 / 0.1 0 ... +360 / ±1 / 0.1 |
| Frequency measurement (U > 50 V) |
46 ... 65 Hz ±0.3 Hz / 0.1 Hz |
| Active energy |
0 ... 999,999 kWh ± 1% of value + 20 digits |
| Apparent energy |
0 ... 999,999 kVAh ± 1% of value + 20 digits |
| Reactive energy |
0 ... 999,999 kVarh ± 1% of value + 20 digits |
|
Harmonics in voltage (relative) 50 - 60 Hz > 80 V AC |
1 - 20th / ± 2% / 0.1% 21 - 50th / ± 4% of value ± 2% / 0.1% |
|
Harmonics in voltage (absolute) 50 - 60 Hz > 80 V AC |
1 - 20th / ± 2% / 0.1% 21 - 50th / ± 4% of value ± 0.5% / 0.1% |
|
Harmonics in current (relative) 50 - 60 Hz > 80 V AC |
1 - 20th / ± 2% / 0.1 % 21 - 50th / ± 4% of value ± 2% / 0.1 % |
|
Harmonics in current (absolute) 50 - 60 Hz > 80 V AC |
1 - 20 th / ± 2% of value ± 0.4 A / 0.1 A 21 - 50 th / ± 4% of value ± 0.4 A / 0.1 A |
|
Total harmonic distortion (THD-F) 50 - 60 Hz > 80 V y > 20 A |
0,0 - 20% / 2% / 0,1% 20.1 - 100% / ± 6% of value ± 1% / 0.1% 100.1 - 999.9% / ± 10% of value ± 1% / 0.1% |
| Maximum clamp opening | 55 mm / 2.2 in |
| Range selection | Automatic |
| Overload indication | "OL" = Overload |
| Memory | 50,000 readings |
| Exit | USB |
| Software and data cable |
included in the delivery. Can be used with Win 2000, XP, ME |
| Display | LCD, 128 x 64 with backlight |
| Power | 2 x 1.5V AA batteries |
| Power consumption | Approximately 10 mA |
| Dimensions | 271 x 112 x 46 mm / 10.6 x 4.4 x 1.8 in |
| Weight | 650 g / 1.4 lb, with batteries |
| Operating conditions | 85% maximum RH / -10 ... 50°C / 14 ... 122°F |
| Protection / Standards | CAT III 600 V / EN 61010-2-032 |
The three-phase clamp meter (Graphic Power Quality Analyzer) PCE-GPA 62 is used for single-phase or three-phase measurements of active, reactive and apparent power, power factor, phase angle, energy, voltage, current as well as peaks and harmonics up to the 50th harmonic of the waveform. The measured values are displayed on the meter's LCD screen, can be recorded and transferred to a computer for further analysis and processing with the help of the software via USB cable. Thanks to the backlit display, the readings are clearly visible even in low-light environments.
- Measures power factor and phase angle, frequency, energy, active, reactive and apparent power (single-phase
or three-phase in symmetrical networks).
- Maximum caliper opening: 55 mm / 2.2 in
- Graphic display
- Automatic shutdown after 15 minutes of inactivity (this function can be disabled)
2 x Individual measuring pins each with 2 m / 6.6 ft cable
2 x Batteries
1 x Carrying case
1 x USB cable
1 x Software (in English)