CODEPCE-GPA 62
CODEPCE-GPA 62
Ammeter Clamp - Multimeter - Datalogger
- Three-phase clamp meter and power analyser
- Real-time power and energy measurement
- Data logger with graphic display
- PC connection and software
- Harmonics up to the 50th
Availability & price
| Code | Availability | excl. VAT | incl. VAT | Certificate | Cart |
|---|---|---|---|---|---|
| PCE-GPA 62 |
€1.043,00
|
€1.293,32
|
= Express from Europe: at our premises in 1-2 working days, from €35 + VAT Express from Europe, from €35 + VAT
- Three-phase clamp meter and power analyser
- Real-time power and energy measurement
- Data logger with graphic display
- PC connection and software
- Harmonics up to the 50th
The PCE-GPA 62 is a three-phase clamp meter and power quality analyser. It measures voltage, current, active, reactive and apparent power, power factor, phase angle, energy, peaks and harmonics up to the 50th. It works on single-phase or three-phase networks.
A backlit graphic display shows the analyser values and stays readable in poor light. Readings can be logged and transferred to a PC for further analysis. The meter is factory-calibrated. A laboratory calibration with ISO certificate can be ordered with the device or for annual recalibration.
Highlights
- Real-time logging of true RMS voltage and current
- Power, energy, power factor, phase angle and frequency
- Single- or three-phase (symmetrical networks)
- Max. conductor diameter 55 mm / 2.2 in
- Backlit graphic display
- Auto power-off after 15 min, can be disabled
- Optional ISO calibration
| AC voltage | |
|---|---|
| Measuring range | 4 ... 600 V |
| Resolution | 0,1 V |
| Accuracy | ±0.5 % ±5 digits |
| Overload | 800V |
| Frequency range | 50 ... 60 Hz |
| Alternating current AC | |
| Measuring range | 4 ... 1500 A |
| Resolution | 0,01 A |
| Accuracy | ±1% ±5 digits |
| Overload | 2000 A |
| Frequency range | 50 ... 60 Hz |
| Active power | |
| Measuring range | 10 ... 999,9 W |
| Resolution | 0,1 W |
| Accuracy | ±1% ±20 digits (>20V and >20 A) / ±2% ±40 digits (<20V <20 A) |
| Measurement range up to | 9,999 kW |
| Measurement range from | 1 kW |
| Resolution | 0,001 kW |
| Accuracy | ±1% ±20 digits (>20V and >20 A) / ±2% ±40 digits (<20V <20 A) W |
| Measuring range | 10 ... 99,99 kW |
| Resolution | 0,01 kW |
| Accuracy | ±1% ±20 digits (>20V and >20 A) / ±2% ±40 digits (<20V <20 A) |
| Measuring range | 100 ... 999,9 kW |
| Resolution | 0,1 kW |
| Accuracy | ±1% ±20 digits (>20V and >20 A) / ±2% ±40 digits (<20V <20 A) |
| Measuring range | 1000 ... 9999 kW |
| Resolution | 1 kW |
| Accuracy | ±1% ±20 digits (>20V and >20 A) / ±2% ±40 digits (<20V <20 A) |
| Reactive power | |
| Measuring range | 10 ... 999,9 VAR |
| Resolution | 0,1 VAR |
| Accuracy | ±2% ±30 digits (>20V and >20 A) / ±3% ±40 digits (<20V <20 A) |
| Measuring range | 1 ... 9,999 kVAR |
| Resolution | 0,001 kVAR |
| Accuracy | ±2% ±30 digits (>20V and >20 A) / ±3% ±40 digits (<20V <20 A) |
| Measuring range | 10 ... 99,99 kVAR |
| Resolution | 0,01 kVAR |
| Accuracy | ±2% ±30 digits (>20V and >20 A) / ±3% ±40 digits (<20V <20 A) |
| Measuring range | 100 ... 999,9 kVAR |
| Resolution | 0,1 kVAR |
| Accuracy | ±2% ±30 digits (>20V and >20 A) / ±3% ±40 digits (<20V <20 A) |
| Measuring range | 1000 ... 9999 kVAR |
| Resolution | 1 kVAR |
| Accuracy | ±2% ±30 digits (>20V and >20 A) / ±3% ±40 digits (<20V <20 A) |
| Phase angle | |
| Measuring range | -180 ... +180 ° |
| Resolution | 0,1 ° |
| Accuracy | ±1 ° |
| Measuring range | 0 ... 360 ° |
| Resolution | 0,1 ° |
| Accuracy | ±1° |
| Apparent power | |
| Measuring range | 10 ... 999,9 VA |
| Resolution | 0,1 VA |
| Accuracy | ±1% ±20 digits (>20V and >20 A) / ±2% ±40 digits (<20V <20 A) |
| Measuring range | 1 ... 9,999 kVA |
| Resolution | 0,001 kVA |
| Accuracy | ±1% ±20 digits (>20V and >20 A) / ±2% ±40 digits (<20V <20 A) |
| Measuring range | 10 ... 99,99 kVA |
| Resolution | 0,01 kVA |
| Accuracy | ±1% ±20 digits (>20V and >20 A) / ±2% ±40 digits (<20V <20 A) |
| Measuring range | 100 ... 999,9 kVA |
| Resolution | 0,1 kVA |
| Accuracy | ±1% ±20 digits (>20V and >20 A) / ±2% ±40 digits (<20V <20 A) |
| Measuring range | 1000 ... 9999 kVA |
| Resolution | 1 kVA |
| Accuracy | ±1% ±20 digits (>20V and >20 A) / ±2% ±40 digits (<20V <20 A) |
| Power factor | |
| Measuring range | 0 ... 1 |
| Resolution | 0.001 |
| Accuracy | ±0.04 (>20 V and >20 A) / ±0.1 (<20 V and <20 A) |
| Active energy | |
| Measuring range | 0 Wh ... 999.999 kWh |
| Resolution | 20 Digits |
| Accuracy | ±1% of Rd + 20 digits |
| Apparent energy | |
| Measuring range | 0 VAh ... 999.999 kVAh |
| Resolution | 20 Digits |
| Accuracy | ±1% of Rd + 20 digits |
| Reactive energy | |
| Measuring range | 0 varh ... 999.999 kVArh |
| Resolution | 20 Digits |
| Accuracy | ±1% of Rd + 20 digits |
| Frequency | |
| Measuring range | 46 ... 65 Hz |
| Resolution | 0,1 Hz |
| Accuracy | ±0.3 Hz |
| Harmonic measurement (harmonics) | |
| Measuring range | 1 ... 50 (ordinal number) |
| General technical data | |
| Measuring functions | HOLD |
| Frequency | 50 ... 60 Hz |
| Display type | LCD graphic display with backlight |
| Display size | 2 Inch |
| Storage medium | Internal memory |
| Storage capacity | 50000 Data records |
| Interface | USB |
| Standard(s) | EN 61010-2-032 |
| Maximum cable diameter | 55 mm |
| Automatic power-off | 15 min |
| Safety standard | CAT III 600V |
| Dimensions | Current clamp opening: max. 55 mm |
| Measuring range selection | Automatic |
| Menu language | English, English (GB) |
| Protection class (device) | IP20 |
| Battery | 2 x 1,5 V AA battery , Alkali-manganese |
| Capacity | 3000 mAh |
| Operating conditions | -10 ... 50 °C , 0 ... 85 % RH |
| Storage conditions | -20 ... 60 °C , 0 ... 75 % RH |
| Dimensions ( L x W x H ) | 271 x 112 x 46 mm |
| Weight | 650 g |
- 1×Three-Phase Clamp Meter PCE-GPA 62
- 2×Isolated measuring pins with 2 m / 6.6 ft of cable each
- 2×Batteries
- 1×Carrying case
- 1×USB cable for a PC
- 1×Software (in English)
- 1×User's manual
Official distributor