Power Analyzer
PCE-PA 8000
| Voltage (ACV) | ||
| Measuring range | Reading | Accuracy |
| 10 V ... 600 V (phase to neutral) | 0.1 V | ±(0.5 % + 0.5 V) |
| 10 V ... 600 V (phase to neutral) | ||
| Current (ACA) | ||
| Measuring range | Reading | Accuracy |
| 20 A |
0.001 A (< 10 A) 0.01 A (≥ 10 A) |
±(0.5 % + 0.1 V) |
| 200 A |
0.01 A (< 100 A) 0.1 A (≥ 100 A) |
±(0.5 % + 0.5 A) |
| 1200 A |
0.1 A (< 1000 A) 1 A (≥ 1000 A) |
±(0.5 A + 5 A) |
| Active power | ||
| Measuring range | Reading | Accuracy |
| 0 KW ... 9.999 KW | 0.001 KW | ±(1 % + 0.008 KW) |
| 10 KW ... 99.99 KW | 0.01 KW | ±(1 % + 0.008 KW) |
| 100 KW ... 999.9 KW | 0.1 KW | ±(1 % + 0.8 KW) |
| 1 MW ... 9.999 MW | 0.001 MW | ±(1 % + 0.008 MW) |
| Apparent power | ||
| Measuring range | Reading | Accuracy |
| 0 KVA ... 9.999 KVA | 0.001 KVA | ±(1 % + 0.008 KVA) |
| 10 KVA ... 99.99 KVA | 0.01 KVA | ±(1% + 0.08 KVA) |
| 100 KVA ... 999.9 KVA | 0.1 KVA | ±(1% + 0.8 KVA) |
| 1 MVA ... 9.999 MVA | 0.001 MVA | ±(1% + 0.008 MVA) |
| Reactive power | ||
| Measuring range | Reading | Accuracy |
| 0 KVAR ... 9.999 KVAR | 0.001 KVAR | ±(1% + 0.008 KVAR) |
| 10 KVAR ... 99.99 KVAR | 0.01 KVAR | ±(1% + 0.08 KVAR) |
| 100 KVAR ... 999.9 KVAR | 0.1 KVAR | ±(1% + 0.8 KVAR) |
| 1 MVAR ... 9,999 MVAR | 0.001 MVAR | ±(1% + 0.008 MVAR) |
| Active energy | ||
| Measuring range | Reading | Accuracy |
| 0 KWh ... 9.999 KWh | 0.001 KWh | ±(1% + 0.008 KWh) |
| 10 KWh ... 99.99 KWh | 0.01 KWh | ±(1% + 0.08 KWh) |
| 100 KWh ... 999.9 KWh | 0.1 KWh | ±(1% + 0.8 KWh) |
| 1 MWh... 9,999 MWh | 0.001 MWh | ±(1% + 0.008 MWh) |
| Apparent energy | ||
| Measuring range | Reading | Accuracy |
| 0 KVAh ... 9.999 KVAh | 0.001 KVAh | ±(2% + 0.008 KVAh) |
| 10 KVAh ... 99.99 KVAh | 0.01 KVAh | ±(2 % + 0.08 KVAh) |
| 100 KVAh ... 999.9 KVAh | 0.1 KVAh | ±(2 % + 0.8 KVAh) |
| 1 MVAh... 9.999 MVAh | 0.001 MVAh | ±(2 % + 0.008 MVAh) |
| Reactive energy | ||
| Measuring range | Reading | Accuracy |
| 0 KVARh ... 9.999 KVARh | 0.001 KVARh | ±(2 % + 0.008 KVARh) |
| 10 KVARh ... 99.99 KVARh | 0.01 KVARh | ±(2 % + 0.08 KVARh) |
| 100 KVARh ... 999.9 KVARh | 0.1 KVARh | ±(2 % + 0.8 KVARh) |
| 1 MVARh... 9,999 MVARh | 0.001 MVARh | ±(2 % + 0.008 MVARh) |
| Power factor | ||
| Measuring range | Reading | Accuracy |
| 0... 1 | 0,01 | ±0.04 |
| Phase angle | ||
| Measuring range | Reading | Accuracy |
| -180º ... 180º | 0.1º | ±1º |
| Frequency | ||
| Measuring range | Reading | Accuracy |
| 45 Hz ... 65 Hz | 0.1 Hz | 0.1 Hz |
| General Features | ||
| Display | 3.7" / 94.0 mm LCD (320 x 240 pixels) with backlight | |
| Electrical parameters | ACV, ACA, active power, apparent power, power factor, phase angle, network frequency | |
| Voltage range | 10 ... 600 ACV, auto range selection | |
| Safety standards | Complies with IEC 1010, CAT III 600 V | |
| ACV input resistance | 10 MΩ | |
| Operating frequency of current clamps | 40 Hz ... 1 kHz | |
| Tested operating frequency of current clamps | 45 Hz ... 65 Hz | |
| Overload protection | ACV / 720 V RMS | |
| ACA | 1300 A with current clamps | |
| Memory | SD card, up to 16 GB | |
| Real-time display refresh rate | 1 second | |
| Data logger | Yes, fully integrated | |
| Data logger sampling rate | Adjustable, 2 ... 7,200 seconds | |
| Data output | USB or RS-232, depending on connection cable | |
| Operating temperature | 0º C ... 50º C / 32 °F ... 122 °F | |
| Operating humidity | < 80 % RH | |
| Power | 8 x 1.5 V AA batteries / AC power supply | |
| Input current |
Meter: 300 mA DC clamp: 34 mA DC |
|
| Clamp jaw diameter | 2" / 50 mm | |
| Weight |
Meter: 948 g / 2.09 lbs (with batteries) Clamp: 467 g / 1.03 lbs (with cable) |
|
| Dimensions | Meter: 225 x 125 x 64 mm / 8.8 x 4.9 x 2.5" | |
| Clamp: 210 x 64 x 33 mm / 8.2 x 2.5 x 1.2" | ||
| Jaw: 86 mm / 3.3" (external) | ||
PCE-PA 8000 Power Analyzer
for measuring current, voltage, and current consumption in real time / Built-in data logger with adjustable rate / Includes current clamps, crocodile clips, test cables, SD card memory
The PCE-PA 8000 is a handheld power analyzer used for testing and inspecting 3-phase / 4-wire, 3-phase / 3-wire, single-phase / 2-wire, and single-phase / 3-wire electrical circuits. This user-friendly power quality meter not only measures multiple electrical parameters in real time but also stores measurement data in .xls format on the included SD memory card for quick and easy data transfer and analysis on a computer.
The PCE-PA 8000 features a clear 3.7" / 94 mm (320 x 240 pixel) LCD display with backlight and provides True RMS measurements of current and voltage, power factor (PF), phase angle (Φ), active power, apparent power, and reactive power. The three included current clamps can be used on cables with a diameter of 2.0" / 50 mm.
- True RMS measurement for ACA, ACV
- True power: W, KW, MW
- VA, KVA, MVA, VAR, KVAR, MVAR
- PF (power factor), phase angle (Φ)
- KWH, KVAH, KVARH, PFH
- Voltage measurement range: 10 ... 600 ACV
- Current measurement range: 0.2 ... 1200 ACA
- Real-time measurement of current, voltage, and power consumption
- Built-in data logger with adjustable rate: 2 ... 7,200 sec.
- Stores measurement data sets with date and time
- Complies with IEC 1010 and CAT III 600 V safety standards
- Includes current clamps, crocodile clip clamps, test cables, SD card memory
3 x Current clamps
4 x Alligator Clips
4 x Test cables
1 x SD Card
8 x 1.5 V AA batteries
1 x AC transformer