Power Analyzer
Voltage (ACV) | ||
Measurement range | Reading | Accuracy |
10 V ... 600 V (phase to neutral) | 0.1V | ±(0.5% + 0.5V) |
10 V ... 600 V (phase to neutral) | ||
Current (ACA) | ||
Measurement range | Reading | Accuracy |
20 A |
0.001 A (< 10 A) 0.01 A (≥ 10 A) |
±(0.5% + 0.1V) |
200 A |
0.01 A (< 100 A) 0.1 A (≥ 100 A) |
±(0.5 % + 0.5 A) |
1200 A |
0.1 A (< 1000 A) 1 A (≥ 1000 A) |
±(0.5A + 5A) |
Active power | ||
Measurement range | Reading | Accuracy |
0 KW ... 9,999 KW | 0.001 KW | ±(1 % + 0.008 KW) |
10 KW ... 99.99 KW | 0.01 KW | ±(1 % + 0.008 KW) |
100 KW ... 999.9 KW | 0.1 KW | ±(1 % + 0.8 KW) |
1MW ... 9.999MW | 0.001MW | ±(1 % + 0.008 MW) |
Apparent power | ||
Measurement range | Reading | Accuracy |
0 KVA ... 9,999 KVA | 0.001 KVA | ±(1 % + 0.008 KVA) |
10 KVA ... 99.99 KVA | 0.01 KVA | ±(1 % + 0.08 KVA) |
100 KVA ... 999.9 KVA | 0.1 KVA | ±(1 % + 0.8 KVA) |
1 MVA ... 9.999 MVA | 0.001 MVA | ±(1 % + 0.008 MVA) |
Idle power | ||
Measurement range | Reading | Accuracy |
0 KVAR ... 9,999 KVAR | 0.001 KVAR | ±(1 % + 0.008 KVAR) |
10 KVAR ... 99.99 KVAR | 0.01 KVAR | ±(1 % + 0.08 KVAR) |
100 KVAR ... 999.9 KVAR | 0.1 KVAR | ±(1 % + 0.8 KVAR) |
1 MVAR ... 9.999 MVAR | 0.001 MVAR | ±(1 % + 0.008 MVAR) |
Active energy | ||
Measurement range | Reading | Accuracy |
0 KWh ... 9,999 KWh | 0.001 KWh | ±(1 % + 0.008 KWh) |
10 KWh ... 99.99 KWh | 0.01 KWh | ±(1 % + 0.08 KWh) |
100 KWh ... 999.9 KWh | 0.1 KWh | ±(1 % + 0.8 KWh) |
1 MWh... 9,999 MWh | 0.001 MWh | ±(1 % + 0.008 MWh) |
Apparent energy | ||
Measurement range | Reading | Accuracy |
0 KVAh ... 9,999 KVAh | 0.001 KVAh | ±(2 % + 0.008 KVAh) |
10 KVAh ... 99.99 KVAh | 0.01 KVAh | ±(2 % + 0.08 KVAh) |
100 KVAh ... 999.9 KVAh | 0.1 KVAh | ±(2 % + 0.8 KVAh) |
1 MVAh... 9,999 MVAh | 0.001 MVAh | ±(2 % + 0.008 MVAh) |
Idle energy | ||
Measurement range | Reading | Accuracy |
0 KVARh ... 9,999 KVARh | 0.001 KVARh | ±(2 % + 0.008 KVARh) |
10 KVARh ... 99.99 KVARh | 0.01 KVARh | ±(2 % + 0.08 KVARh) |
100 KVARh ... 999.9 KVARh | 0.1 KVARh | ±(2 % + 0.8 KVARh) |
1 MVARh... 9,999 MVARh | 0.001 MVARh | ±(2 % + 0.008 MVARh) |
Power factor | ||
Measurement range | Reading | Accuracy |
0... 1 | 0.01 | ±0.04 |
Phase angle | ||
Measurement range | Reading | Accuracy |
-180º ... 180º | 0.1º | ±1º |
Frequency | ||
Measurement range | Reading | Accuracy |
45 Hz ... 65 Hz | 0.1 Hz | 0.1 Hz |
General characteristics | ||
Screen | 3.7" / 94.0 mm LCD (320 x 240 pixels) with backlight | |
Electrical parameters | ACV, ACA, active power, apparent power, power factor, phase angle, grid frequency | |
Voltage range | 10 ... 600 ACV, automatic range selection | |
Safety standards | Complies with IEC 1010, CAT III 600 V | |
ACV input impedance | 10 MΩ | |
Operating frequency of current clamps | 40 Hz ... 1 kHz | |
Tested operating frequency of current clamps | 45 Hz ... 65 Hz | |
Overload protection | ACV / 720V RMS | |
ACA | 1300 A with current clamps | |
Memory | SD card, up to 16 GB | |
Real-time screen refresh rate | 1 second | |
Data logger | Yes, fully integrated | |
Data logger sampling rate | Adjustable, 2 ... 7,200 seconds | |
Data output | USB or RS-232, depending on the connection cable | |
Operating temperature | 0º C ... 50º C / 32 ° F ... 122 ° F | |
Operating humidity | < 80% RH | |
Power supply | 8 x 1.5V AA batteries / AC power supply | |
Input current |
Meter: 300mA DC clamp: 34mA DC |
|
Clamp hole diameter | 2" / 50 mm | |
Weight |
Meter: 948 g / 2.09 lbs (with batteries) Clamp: 467 g / 1.03 lbs (with cable) |
|
Dimensions | Dimension: 225 x 125 x 64mm / 8.8 x 4.9 x 2.5" | |
Clamp: 210 x 64 x 33mm / 8.2 x 2.5 x 1.2" | ||
Jaw: 86mm / 3.3" (external) |
PCE-PA 8000 Power Analyzer
for real-time measurement of current, voltage and power consumption / Built-in data recorder with adjustable rate / Includes current clamps, alligator clips, test leads, SD card memory
The PCE-PA 8000 is a handheld power analyzer used to test and inspect 3-phase/4-wire, 3-phase/3-wire, 1-phase/2-wire and 1-phase/3-wire electrical circuits. This easy-to-use power quality meter not only measures multiple electrical parameters in real time, but also saves the measurement data in .xls format to the included SD memory card for quick and easy data transfer and PC analysis.
The PCE-PA 8000 features an easy-to-read 3.7" / 94 mm (320 x 240 pixels) backlit LCD display and provides True RMS measurements of current and voltage, power factor (PF), phase angle (Φ), active power, apparent power and reactive power. The three included power clamps can be used on 2.0" / 50mm diameter cables.
- True RMS measurement for ACA, ACV
- True power: W, KW, MW
- VA, KVA, MVA, VAR, KVAR, MVAR
- PF (power factor), phase angle (Φ)
- KWH, KVAH, KVARH, PFH
- Voltage measurement range: 10 ... 600 ACV
- Current measurement range: 0.2 ... 1200 ACA
- Measurement of current, voltage and power consumption in real time
- Built-in data recorder with adjustable rate: 2 ... 7,200 sec.
- Stores measurement data sets with date and time
- Complies with IEC 1010 and CAT III 600 V safety standards
- Includes current clamps, alligator clips, test leads, SD card memory
3 x Power Clamps
4 x Alligator Clips
4 x Test Leads
1 x SD Card
8 x 1.5V AA batteries
1 x AC Adapter
1 x Carrying case