CODEPCE-DPD-U/A1
CODEPCE-DPD-U/A1
Relay Output Module for PCE-DPD-U
- Isolated 4 ... 20 mA output
- Active and passive modes
- Precision < 0.5% FS
- 1000 V DC isolation
- Fits Opt1 slot
Same-day dispatchfor orders placed by 15:00
Free shippingon orders over €80 (incl. VAT)
Availability & price
| Code | Availability | excl. VAT | incl. VAT | Cart |
|---|---|---|---|---|
| PCE-DPD-U/A1 |
€91,00
|
€112,84
|
- Isolated 4 ... 20 mA output
- Active and passive modes
- Precision < 0.5% FS
- 1000 V DC isolation
- Fits Opt1 slot
The A1 analogue output module adds an isolated 4 ... 20 mA output to the PCE-DPD-U indicator. It is installed in the Opt1 option slot.
The output works actively or passively. For active use, connect terminal A (+15V DC) and B (mA) with R L < 350 R. For passive use, connect terminal C (GND) and B (mA) with R L < 700 R. Precision is < 0.5% FS, isolation 1000V DC and response time < 100 mSec. plus the indicator response time.
Highlights
- Isolated 4 ... 20 mA analogue output
- Active or passive output operation
- Active: terminals A (+15V DC) and B, R L < 350 R
- Passive: terminals C (GND) and B, R L < 700 R
- Precision < 0.5% FS
- Isolation 1000V DC
- Response time < 100 mSec. plus indicator
- Installs in the Opt1 slot
| Output ranges | 4 ... 20-mA (active and passive) |
|---|---|
| Active output | Connect terminal A (+15V DC) and B (mA) R L < 350 R |
| Passive output | Connect terminal C (GND) and B (mA) R L < 700 R |
| Precision | < 0.5% FS |
| Isolation | 1000V DC |
| Response time | < 100 mSec. + indicator response time |
| Allowed location | Opt1 |